CAFCO®BLAZE-SHIELD® II
CAFCO® BLAZE-SHIELD® II is a cement based spray-applied fire resistive material (SFRM) designed to provide fire resistive ratings for structural steel and concrete in commercial construction.

Applied directly to steel beams, columns and deck, or to concrete surfaces, this product's outstanding value and proven fire resistive performance make it an excellent choice for concealed commercial environments.

BLAZE-SHIELD II is applied exclusively by CAFCO licensed and trained contractors, and our technical staff works closely with building team members to meet all your fire protection needs.

Blaze Shield II
FEATURES   ADVANTAGES   BENEFITS
UL/ULC classified
Noncombustible
Class A rated
40 year history
Proven performance under fire conditions Increased security,
Reduced liability
Only water added
One coat application
Conforms to any surface
 
Fastest and easiest installation Projects are ahead of schedule and under budget
Cement binder
Mineral wool aggregate
15 pcf density
Investigated for exterior use
Best adhesion to roof deck, Able to withstand exterior elements throughout the construction phase Value added protection
PHYSICAL PERFORMANCE
Characteristics  ASTM Method  Standard Performance  Tested Performance* 
Cohesion/Adhesion  E736  150 lb/ft² (7.2 kPa)  399 lb/ft² (19.1 kPa) 
Deflection  E759  No Cracks or Delaminations  No Cracks or Delaminations 
Bond Impact  E760  No Cracks or Delaminations  No Cracks or Delaminations 
Compressive Strength  E761  750 lb/ft² (35.9 kPa)  1700 lb/ft² (81.4 kPa) 
Air Erosion Resistance  E859  Less than 0.025 g/ft² (0.27 g/m²)  0.000 g/ft² (0.000 g/m²) 
Density  E605  15 lb/ft² min. avg (240 kg/m³)  16.5 lb/ft² min. avg (264 kg/m³) 
Combustibility  E136  Noncombustible  Noncombustible 
Corrosion Resistance  E937, Mil. Std. 810  Does Not Promote Corrosion of Steel  Does Not Promote Corrosion of Steel 
*Values represent independent laboratory tests under controlled conditions.
THERMAL PROPERTIES   ACOUSTICAL PROPERTIES
The unique formulation of CAFCO® BLAZE-SHIELD® II makes it a very effective thermal insulator. This benefit is important in reducing heat loss, particularly when applied to the underside of a roof deck, which may allow a reduction in roof insulation.   As an efficient sound-absorbing material, BLAZE-SHIELD II adds value to the fire protection application in areas where high-noise levels are anticipated. Typical acoustical performance is as follows:
Product Conductivity(k)* Resistance (R/inch)
BLAZE-SHIELD II 0.30 @ 75° F
(0.043 W/mK
@ 24°C)
3.33
*When tested in accordance with ASTM C518
 
Product Thickness Base NRC Rating*
BLAZE-SHIELD II 1/2 inch (13mm) Deck & Beam 0.75
BLAZE-SHIELD II 1 inch
(25 mm)
Solid 0.75
*When tested in accordance with ASTM C423